HVAC commissioning checklist
A one-visit checklist for commissioning a new split system, heat pump, or gas furnace. It does not replace the manufacturer's installation instructions; where a target value is needed, record the manufacturer's spec next to your reading.
Job details
- Customer / site
- Date
- Technician
- Equipment (make / model)
- Outdoor unit serial
- Indoor unit / furnace serial
- Refrigerant type
- Thermostat model
Before power-up
- Equipment matches the approved quote and AHRI-matched combination
- Outdoor unit level, on pad or brackets, required clearances met
- Line set sized per manufacturer, insulated, supported, and sealed at wall penetration
- Brazed joints purged with nitrogen; pressure test held with no decay
- Evacuated to the manufacturer's micron target; decay test passed
- Disconnect, breaker size, and wire gauge match nameplate MCA / MOCP
- Condensate drain trapped, pitched, and tested with water; float switch installed if required
- Filter installed, correct size, airflow arrow in the right direction
- Ductwork connected and sealed at the equipment
Startup readings
Run the system at least 15 minutes in each mode before recording final readings.
- Supply voltage (L1-L2)
- Compressor amps (vs RLA)
- Condenser fan amps (vs FLA)
- Indoor blower amps (vs FLA)
- Suction pressure / saturation temp
- Liquid pressure / saturation temp
- Superheat (target)
- Subcooling (target)
- Return air temp
- Supply air temp
- Total external static pressure (vs rated)
- Outdoor ambient temp
Gas heat (if applicable)
- Gas line leak-checked
- Inlet and manifold gas pressure set to spec
- Combustion analysis recorded (O₂, CO air-free)
- Flue / venting pitch, clearances, and termination verified
- Temperature rise within the nameplate range
- CO checked at the supply register and ambient
Controls and safeties
- Thermostat configured for equipment type (stages, heat pump, aux heat)
- Heating, cooling, fan, and emergency heat each cycle correctly
- Defrost board / settings verified on heat pumps
- High / low pressure switches and float switch tested
Leave-behind and closeout
- Photos taken: nameplates, line set, disconnect, drain, filter, gauges at final readings
- Customer shown thermostat operation and filter location / size
- Manuals and warranty registration info left with the customer
- Work area cleaned; old equipment removed per agreement
- Readings and photos attached to the job record
- Customer signature
- Technician signature